Permit: T10CM02531

Parcel: 10705126E

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T10CM02531

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
04/27/2011 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
04/19/2011 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) "SE" CONNECTORS NOT PROPERLY INSTALLED
03/28/2011 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) RECEIVED LETTER OF TORQUE
03/25/2011 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
1) BONDING AT SERVICE TO BE PER 250.102 AND 250.66
2) NEED LETTER OF TORQUE
3) INSTALL AND TERMINATE CONDUCTORS
4) CANNOT STACK GROUND LUGS-ELEVATOR DISCONNECT