Permit: T10CM02524

Parcel: 10705126E

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T10CM02524

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/08/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
02/07/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. COPPER LINE SETS NOT INSULATED OVER DRAIN PAN THIS HAS BEEN AN ON GOING PROBLEM. ANY FUTURE WRITE-UP IN THIS AREA WILL RESULT IN A RE-FEE
DUCT OK TO COVER
02/03/2011 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. REMOVE SHARP-EDGES FROM LINE SETS AT TOP PLATE
2. CONDENSATE PIPE NOT PROPERLY INSTALLED