Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2011 | MECHANICAL - INTERMEDIATE | Approved | PER ERNIE DUARTE BY PHONE CALL, MECHAINCAL IS APPROVED AND FINALED. | |
| 03/22/2011 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 03/04/2011 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FINISH CONDENSATE PIPING 2) DUCT SMOKE DETECTOR SENSING TUBES NOT INSTALLED CORRECTLY 3) HOLES ARE FACING WRONG DIRECTION 4) THE TUBES ARE HOLD IN PLACE WITH TAPE, WHERE ARE THE FLANGES ON THE END OF THE TUBES THAT SCREW INTO THE SMOKE DETECTOR POINT OF CONNECTION ? 5) DUCT SMOKE DETECTORS MUST BE CONNECTED INTO THE FIRE ALARM SYSTEM 6) PROVIDE TEST REPORT AFTER CONNECTION BY FIRE ALARM COMPANY 7) THERE IS NOT OUTSIDE AIR BEING INTRODUCED INTO THESE UNITS 8) PLANS SHOW ADDITIONA AIR IS REQUIRED 9) PROVIDE AIR BALANCE REPORT 10) ARE HEAT STRIPS INSTALLED ? |