Permit: T10CM02513

Parcel: 12701005D

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T10CM02513

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/27/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/16/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROTECT VDV CABLING RACEWAYS FROM SHARP METAL EDGES
2) FINISH SUPPORTING VDV CABLING 725.3 & 24, 800.3 & 24 AND 300.11
3) SUPPORT M/C CABLE PER CODE 330.30
4) OK WALLS
09/15/2010 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled