Inspection History: ELECTRIC - CONSTRUCTION POWER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/01/2010 | ELECTRIC - CONSTRUCTION POWER | Approved | IVRS - Inspection :* | |
| 09/29/2010 | ELECTRIC - CONSTRUCTION POWER | Denied | IVRS - Inspection : See detailed listing on site.| 999* TRAILER: 1) A GROUNDING ELECTRODE SYSTEM NEEDED AT TRAILER 2) FILL UNUSED OPENING IN BOTTOM OF PANEL 3) REMOVE BONDING SCREW 4) BREAKER TO BE LISTED FOR USE BY MANUFACTURE PANEL: 1) LABEL PANEL-PERMANENT ADDRESS LABEL BREAKER 2) INSTALL BOND JUMPER AND LUG TO BOND BUSHING ON RISER |