Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2010 | MECHANICAL - FINAL | Approved | ||
| 09/22/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED TO SEE ROOF TOP DRAWING APPROVED BY CITY OF TUCSON |
|
| 09/15/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A TRAP ON CONDENSATE DRAIN PER NOT ON FAN COIL. PROVIDE AIR OVERFLOW SENSOR 2) MARK UNIT DATA PLATE ON FAN COIL AND PROVIDE PROPER OVER CURRENT PROTECTION 3) INSULATE SHEET METAL SLEEVE ON FAN COIL 4) SECURE THE CONDENSOR AND ANGLE IRON FRAME TO THE ROOF 5) TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND 6) PROVIDE A ROOF JACK AT ELECTRIC PENETRATION THRU ROOF 7) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX 8) PROVIDE THE REQUIRED ROOF TOP DRAWING FOR NEW A/C 9) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF 10) SEAL DOOR TO CLOSET AT RETURN AIR PLATFORM |