Permit: T10CM02474

Parcel: 134161450


Addresses:

7352 E 19TH ST

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/14/2011 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999- SUPPORT MAST WITH A LISTED SUPPORT
-6 AWG MINIMUM FOR BONDING CONDUCTOS FOR GAS AND WATER
- LB CONNECTORS OVERFILLED TO OLD PANEL
06/06/2011 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
GAS AND WATER BOND NEEDED
INSTALL SERVICE CONDUCTORS
SUPPORT MAST WITH LISTED SUPPORTS
SECURE RISER ABOVE PANEL IN TWO PLACES
11/08/2010 ELECTRIC - SERVICE UPGRADE Cancelled CANCELLED PER CONTRACTOR JOHN #551-6868
11/08/2010 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*