Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/28/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) LABELING TO BE PER 690.17 ON ALL EQUIPMENT 2) CONDUCTORS TO BE PER 200.6 & 250.119 3) INSTALL MAIN BONDING JUMPER AT SERVICE DISCONNECT 4) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL/COMINER PANEL 5) BOND METAL PER 250.64 (E) ROOF: 1) CANNOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8 AND CLEAN SURFACE 250.12 2) VERIFY WIR NOT FILL CAPACITY 3) CANNOT ADD HOLE TO CAST METAL BOXES-USE ONLY MANUFACTURE SUPPORTED OPENINGS 4) TIGHTEN LOOSE FITTINGS 5) PLEASE VERIFY GROUND LUG DETAIL FOR MOUNTING |