Permit: T10CM02469

Parcel: 123051170

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/04/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/28/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) LABELING TO BE PER 690.17 ON ALL EQUIPMENT
2) CONDUCTORS TO BE PER 200.6 & 250.119
3) INSTALL MAIN BONDING JUMPER AT SERVICE DISCONNECT
4) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL/COMINER PANEL
5) BOND METAL PER 250.64 (E)
ROOF:
1) CANNOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8 AND CLEAN SURFACE 250.12
2) VERIFY WIR NOT FILL CAPACITY
3) CANNOT ADD HOLE TO CAST METAL BOXES-USE ONLY MANUFACTURE SUPPORTED OPENINGS
4) TIGHTEN LOOSE FITTINGS
5) PLEASE VERIFY GROUND LUG DETAIL FOR MOUNTING