Permit: T10CM02468

Parcel: 105102410

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Permit Number - T10CM02468

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
12/29/2010 ELECTRIC - PROGRESS Approved PER EL FINAL
11/16/2010 ELECTRIC - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT WIRES NEED TO BE TIEDF OFF AT BOTH ENDS PER 300.11 NEC
2) 2 X 4 LAY IN FIXTURES NEED TO BE SECURED TO GRID 410.16 NEC., ALSO WIRES TIED OFF AT ADJACENT CORNERS OF FIXTURES NEED TO THREAD THRU HOLES PROVIDED BY FIXTURE, DO NOT USE BEND OUT TABS FOR WIRE SUPPORTS
3) THERM, LV, CABLING NEEDS TO BE SUPPORTED TO BLDG STRUCTURE, OFF GRID 725-800 NEC
10/29/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*