Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T10CM02454
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/30/2011 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 821 IN WALLS OK 2) SECURE AND ISOLATE TUBING ABOVE CEILING |
|
09/28/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) 821, SECURE SHOWER DIVERTER VALVE AND TURN WATER ON FOR INSPECTION 2) REMOVE FURNCO COUPLING ON KIT SINK DRAIN IN WALLS 3) SEAL ABANDONED FLOOR PENETRATIONS |
|
09/08/2011 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* UNIT 821 WATER RE-PIPE INSPECTION: 1) NEW TUB AND SHOWER DIVERTER REQUIRED TO BE TEMP PLUS PSI BALANCED 2) PEX MAY NOT CONTACT METAL 3) SECURE ALL TUBING AND CONNECTIONS 4) PLUG OPEN SEWER DRAIN PIPES-ONLY WARNING 5) FERNCO COUPLING NOT APPROVED FOR USE INSIDE BLDG 6) YARD WATER SHALL HAVE 12" OF COVER 7) ? MAY NOT THREAD INTO PVC ?-EXPOSE FOR INSPECTION 8) RE-INSTALL GROUNDING |
|
08/31/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
05/25/2011 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) BLDG IN ORIGINAL CONDITION, NEW WORK HAS NOT BEEN DONE 2) PLAN INDICATES WATER HEATER REPLACEMENT |