Permit: T10CM02454

Parcel: 126030020


Addresses:

821 N SWAN RD


Inspection Status: Partial Approval

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T10CM02454

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Partial Approval

Date Description Inspector Results Comments
09/30/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 821 IN WALLS OK
2) SECURE AND ISOLATE TUBING ABOVE CEILING
09/28/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) 821, SECURE SHOWER DIVERTER VALVE AND TURN WATER ON FOR INSPECTION
2) REMOVE FURNCO COUPLING ON KIT SINK DRAIN IN WALLS
3) SEAL ABANDONED FLOOR PENETRATIONS
09/08/2011 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
UNIT 821 WATER RE-PIPE INSPECTION:
1) NEW TUB AND SHOWER DIVERTER REQUIRED TO BE TEMP PLUS PSI BALANCED
2) PEX MAY NOT CONTACT METAL
3) SECURE ALL TUBING AND CONNECTIONS
4) PLUG OPEN SEWER DRAIN PIPES-ONLY WARNING
5) FERNCO COUPLING NOT APPROVED FOR USE INSIDE BLDG
6) YARD WATER SHALL HAVE 12" OF COVER
7) ? MAY NOT THREAD INTO PVC ?-EXPOSE FOR INSPECTION
8) RE-INSTALL GROUNDING
08/31/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
05/25/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) BLDG IN ORIGINAL CONDITION, NEW WORK HAS NOT BEEN DONE
2) PLAN INDICATES WATER HEATER REPLACEMENT