Permit: T10CM02452

Parcel: 12709012E

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T10CM02452

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/30/2010 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
09/29/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLANS CALL FOR NEW FIXTURE-OPEN TO INSPECT
2) SECURE FIXTURE TO GRID 4 ON CORNERS 410.16
3) SUPPORT VDV CABLES 725.3 + 24, 760.3 + 24, 800.3 + 24 AND 300.11
4) BOXES MORE THAN 1/4" IN NON COMBUSTIBLES 314.20 OR MORE THAN 1/8" 314.21
5) REVISE PANEL SCHEDULE 408.4
6) FIXTURES ON PLANS DO NOT MATCH WHAT IS INSTALLED EM TYPES