Permit: T10CM02427

Parcel: 108214240

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T10CM02427

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2010 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
1) BATHROOM EXHAUST MUST BE ON A TIME CLOCK PER PLANS
2) NO COMBUSTIBLE MATERIAL ALLOWED IN A PLENIUM CEILING. NO REASON FOR AREA ABOVE BATHROOMS TO BE A PLENIUM. REMOVE RETURN AIR TRANSFER DUCT AND SEAL OPENING IN WALL. OK TO SHEETROCK OVER ABS ABOVE T-BAR IN BREAKROOM. WILL CHECK AT FINAL