Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T10CM02427
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) BATHROOM EXHAUST MUST BE ON A TIME CLOCK PER PLANS 2) NO COMBUSTIBLE MATERIAL ALLOWED IN A PLENIUM CEILING. NO REASON FOR AREA ABOVE BATHROOMS TO BE A PLENIUM. REMOVE RETURN AIR TRANSFER DUCT AND SEAL OPENING IN WALL. OK TO SHEETROCK OVER ABS ABOVE T-BAR IN BREAKROOM. WILL CHECK AT FINAL |