Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/16/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE PLMG PERMIT + GAS PRESS TEST 2. PROVIDE CITY OF TUCSON STAMPED ROOF LOAD DRAWINGS. 3. BLOCKING ON 3/4' PVC NOT TO EXCEED 48' 4. PROVIDE SEDIMENT TRAP ON GAS PIPING TO UNIT 5. PROVIDE APPROVED DUCT INSULATION, 1' DUCT LINER ONLY PROVIDES AN R-VALVE OFR-4.2, THE MIN REQUIREMENT IS R-8, R-8 IS 2" DUCT LINER 6. ELECTRICAL TO UNIT AND SERVICE OUTLET OK |