Permit: T10CM02426

Parcel: 126171610

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/19/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/16/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE PLMG PERMIT + GAS PRESS TEST
2. PROVIDE CITY OF TUCSON STAMPED ROOF LOAD DRAWINGS.
3. BLOCKING ON 3/4' PVC NOT TO EXCEED 48'
4. PROVIDE SEDIMENT TRAP ON GAS PIPING TO UNIT
5. PROVIDE APPROVED DUCT INSULATION, 1' DUCT LINER ONLY PROVIDES AN R-VALVE OFR-4.2, THE MIN REQUIREMENT IS R-8, R-8 IS 2" DUCT LINER
6. ELECTRICAL TO UNIT AND SERVICE OUTLET OK