Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/02/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) CANNOT USE PLASTIC BOXES WITH METALLIC RACEWAYS NEC 314.3 2) OK PV SYSTEM |
|
| 11/29/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) OK GROUND RODS 2) OK WATER BOND 3) LINE SIDE INSPECTION ONLY, RECALL FOR BRANCH CIRCUITS WHEN READY |