Permit: T10CM02384

Parcel: 126030060


Addresses:

801 N SWAN RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10CM02384

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/24/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
02/23/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
02/23/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) DO NOT USE FLEX DUCT FOR DRYER VENT
2) PROVIDE PROPER FUSING
02/15/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
02/08/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE A DRYER VENT
PROVIDE SUN SHEILDS OVER CANVAS CONNECTORS
REDO ROOF TOP CONDESATE DRAINS + USE PURPLE PRIMER PRIOR TO GLUE PAINT ALL EXPOSED PVC W LATEX PAINT MARK UNIT DATA PLATES W PROPER HEAT STRIP INSTALLS + FUSE ACCORDINGLY
PROVIDE MIN R8 DUCT LINES IN EXPOSED DUCT ON ROOF
DISCONNECT + CIRCUIT BREAKER WILL NEED TO BE CHANGES.
SECURE ANGLE IRON STANDS TO THE ROOF.