Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T10CM02384
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/06/2011 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) CORRECTIONS INSIDE UNITS HAVE BEEN MADE |
|
12/30/2010 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE 2" DUCT LINER OR ROOF TOP DUCT (R-8), PROVIDE R-8 ON ALL DUCT IN ATTIC SPACE 2) CEILING DIFFUSERS ARE TO BE FRAMED ON 3 SIDES 3) ALL PVC PIPE IS TO BE PRIMERED AT ALL JOINTS, PRIMER IS TO BE PURPLE IN COLOR 4) WHEN TIEING 2 OR MORE CONDENSATE LINES TOGETHER, INCREASE LINE SIZE TO 1" 5) CONDENSATE CANNOT TERMINATE AT A HARD SURFACE 6) T-STAT WIRE NOT INSTALLED 7) ALL CANS AND FITTINGS ARE TO BE INSULATED 8) PROVIDE FULL RADIUS BENDS ON FLEX DUCT |