Permit: T10CM02384

Parcel: 126030060


Addresses:

801 N SWAN RD


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T10CM02384

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/08/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
01/06/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK EXCEPT THAT SHOWER DIVERTERS REQUIRE STOPS, AND CLOSET FLANGES SOT ON FF AND SECUREED, WILL INPECT AFTER FF
12/27/2010 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LEAK BEHIND TUB
2) T & P DRAIN NOT SIZED PROPERLY SECURE DIVERTERS
3) SEPERATE STOPS REQUIRED
4) INSTALL ISOLATION SUPPORTS AT TOP PLATE PENETRATIONS
5) INSTALL HB VAC BREAKER
6) INSTALL TRAP PRIMER AT FD
12/09/2010 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DWV WITH TEST ONLY THRU ROOF OK
2) INSTALL TRAP PRIMER AND FOAM WRAPS PRIOR TO CONCRETE
12/08/2010 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/06/2010 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) NO TEST ON SYSTEM
2) SHADE PIPING U.G., NO VOIDS OR BRIDGING PERMITTED