Permit: T10CM02379

Parcel: 121040930


Addresses:

5702 E SENECA ST

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/10/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CORRECT ITEMS #2 & 3
09/29/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE APPROVED SUPPORTS PROPERLY SECURED TO ROOF AT CORRECT INTERVALS FOR TUBING USED FOR SOLAR PIPING
2) INSULATION ON POTABLE PIPING TO BE ON ENTIRE PIPING SYSTEM EXPOSED TO FREEZING, INSULATION TO9 BE SEALED AT JOINTS AND PROTECTED FROM SUN EXPOSURE
3) INSTALL DRAFT HOOD ON WATER HEATER CORRECTLY AND PROVIDE CORRECT PERM. CAP ON EXISTING OLD FURNACE VENT CONNECTION OR CORRECTLY VENT WATER HEATER USING APPROVED INCREASER/REDUCER
4) PROVIDE 1" AIR GAP FROM TOP LIP OF DRAIN PAN FOR T & P RELIEF PIPING