Inspection Status: Approved
Inspection History: PLUMBING - ROOF DRAINS
Permit Number - T10CM02371
Inspection Description - PLUMBING - ROOF DRAINS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2011 | PLUMBING - ROOF DRAINS | Approved | IVRS - Inspection :* | |
08/19/2011 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* STRAINERS CO PLUGS ROUGH SOIL HISTORY TEST ON RWL THRU ROOF OK |
|
08/01/2011 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 1) INSPECTOR WILL ACCEPT SK DRAWING, BE SURE AND RED LINE APPROVED PLAN |
|
07/18/2011 | PLUMBING - ROOF DRAINS | Not ready for Inspection | IVRS - Inspection :* | |
07/14/2011 | PLUMBING - ROOF DRAINS | Not ready for Inspection | IVRS - Inspection :* 1. CAST IRON RAINWATER LEADERS MAY NOT HAVE BACK PITCH. 2. CAST IRON IS TO BE LAID ON A FIRM BED BRIDGING NOT PERMITTED-UNABLE TO VERIFY TEST. |
|
04/07/2011 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 1) THIRD COLUMN CONNECTED TO UNDERGROUND OK-OK TO COVER |
|
03/15/2011 | PLUMBING - ROOF DRAINS | Partial Approval | 1. OK TO POUR THE THIRD COLUMN. | |
03/09/2011 | PLUMBING - ROOF DRAINS | Partial Approval | Z COLUMNS OK TO POUR | |
02/02/2011 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 3-6" PVC RAINWATER LEADERS STUBBED OUT OF COLUMNS WATER TEST OK |
|
01/25/2011 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* |