Permit: T10CM02371

Parcel: 117050020


Addresses:

400 N 2ND AV


Inspection Status: Approved

Inspection History: PLUMBING - ROOF DRAINS

Permit Number - T10CM02371

Inspection Description - PLUMBING - ROOF DRAINS

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2011 PLUMBING - ROOF DRAINS Approved IVRS - Inspection :*
08/19/2011 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
STRAINERS
CO PLUGS
ROUGH SOIL HISTORY
TEST ON RWL THRU ROOF OK
08/01/2011 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
1) INSPECTOR WILL ACCEPT SK DRAWING, BE SURE AND RED LINE APPROVED PLAN
07/18/2011 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
07/14/2011 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*

1. CAST IRON RAINWATER LEADERS MAY NOT HAVE BACK PITCH.
2. CAST IRON IS TO BE LAID ON A FIRM BED BRIDGING NOT PERMITTED-UNABLE TO VERIFY TEST.
04/07/2011 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
1) THIRD COLUMN CONNECTED TO UNDERGROUND OK-OK TO COVER
03/15/2011 PLUMBING - ROOF DRAINS Partial Approval 1. OK TO POUR THE THIRD COLUMN.
03/09/2011 PLUMBING - ROOF DRAINS Partial Approval Z COLUMNS OK TO POUR
02/02/2011 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
3-6" PVC RAINWATER LEADERS STUBBED OUT OF COLUMNS WATER TEST OK
01/25/2011 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*