Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T10CM02371
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/03/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/02/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/01/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) RACE WAY TO BE CONTINOUS TO BOX 2) PANEL DIRECTORY TO BE PER 408.4 3) SUPPORT FEEDER CONDUIT 4) FILL UNUSED OPENING PANEL PB1 5) CHECK BOX FILL 6) PLEASE OPEN CEILING |
|
07/26/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOND BUSHINGS AT CONCENTRICS OVER 250V 250.97 2) LABEL DISCONNECTS 3) NEED ACCESS TO LIGHTING |