Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/19/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 10/14/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 10/08/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SECURE FIXTURES TO GRID 410.16 2) SUPPORT M/C FIXTURE WHIPS 300.11 3) FIXTURE WHIP CONDUCTORS NOT LARGE ENOUGH TO CARRY DAISY CHAIN LOADS 4) BOXES OVER FILLED 5) CORDS NOT ALLOWED ABOVE CEILING 400.7 6) A REFEE MAY BE ASSESED |
|