Permit: T10CM02360

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10CM02360

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/08/2010 ELECTRIC - FINAL Approved
11/05/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED 100 A CKT MAIN BREAKER PANEL 'H'
11/04/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FUSES AT 480V DISC. AND AT SES NEED TO BE 150A
11/03/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PLANS CALL FOR 150A MAIN PANEL H
2) CONTRACTOR TO OPEN EQUIPMENT CONTACTOR J-BOX FOR INSPECTION
3) WHEN USING METAL RACEWAY FOR GROUNDING ELECTRODE CONDUCTOR (X-FORMER) INSTALL BOND BUSHING BOTH ENDS PER NEC 250