Permit: T10CM02330

Parcel: 122091270


Addresses:

4134 E LESTER ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/16/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/09/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) MAINTAIN WORKING CLEARANCE IN FRONT OF PV SERVICE 110.26
2) GROUNDING ELECTRODE CONDUCTOR IN METAL RACEWAYS TO BE PER 250.64 (E)
3) LABELING TO BE 690.17
4) #8 + LARGER TO STRANDED CONDUCTOR 310.3