Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/02/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
| 09/01/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PLEASE PROVIDE PAPERWORK FOR SPLICE CONNECTOR GROUND TO VERIFY INSTALLATION AND LISTED 2) FINISH #3 & 4 PER CODES |
|
| 08/31/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PROPERLY TERMINATE STRANDED CONDUCTORS UNDER SCEWS 2) TERMINATE GROUNDING ELECTRODE CONDUCTOR AT LABELED TERMINAL 3) BOND METALIC RACEWAY WITH GROUNDING ELECTRODE CONDUCTOR PER 250.64 (E) 4) LABELING TO BE PER 690.17 5) GROUND LUGS AT UNIRACK SPLICE NOT CORRECTLY INSTALLED |