Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) SUPPORT FLEX DUCTS EVERY 5'. UNIT #7 HAS NO SUPPORT ON DUCTS 2) FLEX DUCTS NOT TO EXCEED 8' 3) PROVIDE A LETTER FROM ENGINEER TO9 ALLOW LONGER FLEX AND STRAIGHT START COLLARS-WILL CHECK AT FINALS |