Permit: T10CM02261

Parcel: 12510006C


Addresses:

3699 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
03/23/2011 ELECTRIC - ABOVE CEILING Approved
03/11/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUPPORT VDV CABLING 725.3 + 24, 800.3 + 24, 300.11
2) PROTECT CONDUCTOR IN RACEWAYS 300.4
3) PANEL DIRECTORIES TO BE PER 408.4
4) OK ABOVE CEILING GRID
5) RECEIVED MONEY ORDER #14-232783414 FOR $340.00
6) EXISTING RELOCK AND M/C CABLES LAYING ON GRID UNSUPPORTED
02/17/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/15/2011 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
01/25/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/19/2011 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) MET CONTRACTORS AND DISCUSSED JOB