Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2011 | ELECTRIC - INTERMEDIATE | Approved | ||
| 02/24/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 02/11/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) LABEL TEMP UNIT TO MATCH BREAKERS 2) IDENTIFY GROUNDED CONDUCTOR AND UNGROUNDED 277/480 CONDUCTOR BROWN, ORANGE AND YELLOW 3) TEMP SERVICE CASES |
|
| 01/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SUPPORT DROPS INTO WALK INS 2) OK WALLS LABEL ROOM |