Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T10CM02260
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/07/2012 | FIRE - FINAL | Approved | PER CONVERSATION WITH CSCHULTZ. HOOD & DUCT INSPECTIONS COMPLETED AND 1999 PERMIT HAS BEEN CLOSED. | |
06/06/2012 | FIRE - FINAL | Denied | All corrections done with the exception of clearing out the following permit T99BU00553 | |
03/14/2012 | FIRE - FINAL | Denied | 1. Southside kitchen egress door remove double cylinder key dead bolt lock and install a thumb style turn lock. 2. Both hood systems are pass due on inspections this is done every 6 months. 3. North side kitchen egress door remove slide bolt lock. 4. West cleaning area egress door remove double cylinder dead bolt lock and install thumb style lock. 5. Outside front sign wire not water tight need to make water tight. 6. Outside patio electrical needs to be water tight, open boxes and broken conduit, outlets not GFCI protected. 7. Check on expired permit # T99BU00553 for the hood system. |