Permit: T10CM02260

Parcel: 137052880


Addresses:

5118 S 12TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T10CM02260

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
07/05/2012 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/06/2012 ELECTRIC - SERVICE UPGRADE Partial Approval GROUNDS NEED TO BE SUPPORTED TO STRUCTURE.
NO LOADS CONNECTED YET
06/05/2012 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TIGHTEN ALL LUGS
2) GET TO GROUNDED CONDUCTOR TERM. MAIN DISC. SW SE NOTE #4 3/15/12
3) INSTALL BOND JUMPERS NOTE #1 5/23/12
05/23/2012 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BOND JUMPERS NOT INSTALLED IN CT, DISC. SW SUPPLY SIDE
2) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE ON NEUTRAL TERMINAL BAR IN MAIN SERVICE DISCONNECT
3) HAVE ELECTRICAL CONTRACTOR ON SITE NEXT INSPECTION TO OPEN ALL EQUIPMENT FOR INSPECTION
4) PLANS/PERMIT ON SITE
03/15/2012 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1) NEED BRACE/SUPPORT BELOW ROOF
2) NEED REJECTION PINS
3) BONDING JUMPER TO BE PER 250.102 AND 250.66
4) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE TO GROUNDED TERMINAL
5) CHECK PANEL NEXT TIME
03/14/2012 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR TO RESCHEDULE PER RAY CAMACHO AND DAN SANTACRUZ
2) 3 PHASE 400 AMP SERVICE