Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T10CM02260
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/05/2012 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
06/06/2012 | ELECTRIC - SERVICE UPGRADE | Partial Approval | GROUNDS NEED TO BE SUPPORTED TO STRUCTURE. NO LOADS CONNECTED YET |
|
06/05/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN ALL LUGS 2) GET TO GROUNDED CONDUCTOR TERM. MAIN DISC. SW SE NOTE #4 3/15/12 3) INSTALL BOND JUMPERS NOTE #1 5/23/12 |
|
05/23/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOND JUMPERS NOT INSTALLED IN CT, DISC. SW SUPPLY SIDE 2) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE ON NEUTRAL TERMINAL BAR IN MAIN SERVICE DISCONNECT 3) HAVE ELECTRICAL CONTRACTOR ON SITE NEXT INSPECTION TO OPEN ALL EQUIPMENT FOR INSPECTION 4) PLANS/PERMIT ON SITE |
|
03/15/2012 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) NEED BRACE/SUPPORT BELOW ROOF 2) NEED REJECTION PINS 3) BONDING JUMPER TO BE PER 250.102 AND 250.66 4) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE TO GROUNDED TERMINAL 5) CHECK PANEL NEXT TIME |
|
03/14/2012 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) CONTRACTOR TO RESCHEDULE PER RAY CAMACHO AND DAN SANTACRUZ 2) 3 PHASE 400 AMP SERVICE |