Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/19/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STAPLE WIRES BEHIND ELECTRIC PANEL 2) GROUND METAL BOXES 3) INSTALL GAS AND WATER BONDS 4) NEED BRACKETS ON MAST 5) NEED ADDRESS ON PANEL 6) SCHEDULE 40 NEEDS PHYSICAL PROTECTION OR CHANGE TO SCHEDULE 80 7) SEPERATE GROUNDS AND NEUTRAL IN NEW SUB PANEL |