Permit: T10CM02256

Parcel: 12909146C

Inspection Status: Cancelled

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T10CM02256

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Cancelled

Date Description Inspector Results Comments
12/23/2010 MECHANICAL - INTERMEDIATE Cancelled IVRS - RI canceled
12/23/2010 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
12/22/2010 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/23/2010 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO SEE ALL CORRECTIONS ABOVE CEILING
2) WHERE ARE THE BEADED COLLARS ON CEILING DIFFUSERS ?
11/09/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROVIDE MINIMUM 2" BEADED COLLARS ON ALL FLEX DUCT CONNECTIONS PER INSTALL INSTRUCTIONS
2) PROVIDE FULL RADIUS ON FLEX DUCT BENDS
3) FLEX DUCT SUPPORT NOT TO EXCEED 5', REMOVE ALL SAG.
4) UNIT 203 RETURN DUCT NOT SIZED CORRECTLY
5) UNIT 205 RETURN DUCT NOT SIZED CORRECTLY
6) PROVIDE ENGINEERS WRITTEN APPROVAL FOR ALL CHANGES
7) SEAL ALL DUCTS