Permit: T10CM02256

Parcel: 12909146C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/22/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/03/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/23/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CEILINGS CLOSED WITHOUT CLEARANCE OF INSPECTION-PLEASE REOPEN
2) NO PLAN REVISION ON SITE
11/17/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) VDV CABLING TO BE PER 300.11-CANNOT BE SWINGING
2) NEED PLAN REVISION
11/10/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROPERLY INSTALL SERVICE NIPPLE BUSHING
2) SERVICE EQUIPMENT DIFFERENT THAN PLANS-TYPE AND FUSES
3) OK M/C AND CONDUIT SUPPORTS
11/09/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) INDEPENDANCY SUPPORT VDV CABLING AND SUPPORT PER CODE
2) SUPPORT M/C WITHIN 12" OF BOXES
3) SUPPORT CONDUITS PER CODE
4) OK 2 X 4 LIGHTS
5) NOTE: 314.20 WILL APPLY
6) RECEIVED M/C LETTER
10/14/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/12/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) USE APPROVED METHODS TO SUPPORT M/C CABLE THHN COPPER IS NOT
2) PROTECT VDV CABLING FROM SHARP METAL EDGES
3) PROTECT M/C CABLE IN SHALLOW STUDS
4) PROVIDE AUTHORIZATION TO USE M/C CABLE PLANS CALL FOR 3/4" MINIMUM CONDUIT