Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/15/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO ACCESS-ALL GATES LOCKED |
|
| 12/14/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) ARC FAULT PROTECT BEDROOM AND SMOKE ALARM CIRCUITS |
|
| 11/29/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO POWER 2) TPR TO EXTERIOR 3) HAMMER ARRESTORS LAUNDRY 4) DRIP LEG APPLIANCES 5) INSTALL DISHWASHER |
|
| 11/24/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY BILL |
|
| 11/19/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/15/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/09/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUB-PANEL NOT ALLOWED IN CLOSET 2. NEED PERMIT FOR ALL NEW WORK (COMMENTS TRANSFERRED FROM T10EL01622) |
|
| 07/30/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) A LISTED MAST BRACE KIT IS NEEDED 2) MAINTAIN WORKING CLEARANCE 110.26-PLUMBING BELOW PANEL 3) NO LOADS AT THIS TIME (COMMENTS TRANSFERRED FROM T10EL01622) |