Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T10CM02216
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) TAP GROUNDING ELECTRODE CONDUCTOR OUTSIDE SERVICE PANELS 2) DIRECT BURRIAL NEEDS TO BE 24" BELOW GRADE 3) LAUNDRY ROOM AND GARAGE FEEDER NEEDS TO BE 4 WIRE IF USING 110V AS WELL AS 240V OUTLETS 4) ID FEEDERS IN J-BOX UNIT 1633 & 1631 |
|
09/30/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* THESE NOTES ARE FOR BOTH ADDRESSES ON THIS PERMIT: 1) DOG IN YARD-NO MSG AND NO ANSWER AT DOOR |
|
09/08/2010 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE GROUND ON RISER 2) 2 GROUND RODS NOT 1 3) GROUND NOT NEEDED IN RISER-REMOVE 4) BOND ON NIPPLE BETWEEN METER BASES 5) 2 PIPES NOT ONE FOR SUB PANELS |