Permit: T10CM02196

Parcel: 11103058B

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
07/25/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
07/15/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SEALED JOINTS ON DUCTING OK
2) 2ND LAYER OF FIRE WRAP IS OK
3) LETTER FROM ENGINEER OK
05/31/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/18/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK TO COVER DUCT IN NORTH SIDE SOFFITS PENDING APPROVAL FROM MECH. ENGINEER TO USE DOVE TAILS
05/17/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE 45 DEGREE BRANCH TAPS AS PER PLANS
2) PROVIDE SPIN IN COLLOARS AS PER PLANS
3) INSULATE LINEAR CANS TO MINIMUM 4.2 AS PER PLANS AND CODE REQUIREMENTS
4) FLEX DUCT SUPPORT NOT TO EXCEED 5'
5) ANY CHANGES TO PLANS, SPECS, DETAILS REQUIRE WRITTEN APPROVAL FRO MECH. ENGINEER OF RECORD