Permit: T10CM02188

Parcel: 13314236C


Addresses:

7091 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/21/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL
10/19/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TERMINATE CONDENSATE HOSE FROM MINI SPLIT FAN COIL INTO COPPER WITH A FITTING
2) PROVIDE HAIL GUARDS ON A/C UNITS PER PLANS
3) MARK UNIT DATA PLATES WITH PROPER HEAT STRIP INSALLED AND FUSE ACCORDINGLY
4) PERMANENTLY I.D. A/C EQUIPMENT
5) PROVIDE PERMISSION TO USE RHEEM EQUIPMENT AND AIR BALANCE OK
10/14/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
08/27/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) OK FOR FINAL PHASE I
08/26/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) CONDENSATE CANNOT TERMINATE INTO ANOTHER SUITE
2) EXHAUST FAN TO BE ON A TIME CLOCK
3) A/C UNIT NOT PER PLAN EQUIPMENT SCHEDULE AND NOTES
4) AIR BALANCE OK