Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T10CM02188
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/21/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FINAL |
|
10/19/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TERMINATE CONDENSATE HOSE FROM MINI SPLIT FAN COIL INTO COPPER WITH A FITTING 2) PROVIDE HAIL GUARDS ON A/C UNITS PER PLANS 3) MARK UNIT DATA PLATES WITH PROPER HEAT STRIP INSALLED AND FUSE ACCORDINGLY 4) PERMANENTLY I.D. A/C EQUIPMENT 5) PROVIDE PERMISSION TO USE RHEEM EQUIPMENT AND AIR BALANCE OK |
|
10/14/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
08/27/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) OK FOR FINAL PHASE I |
|
08/26/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CONDENSATE CANNOT TERMINATE INTO ANOTHER SUITE 2) EXHAUST FAN TO BE ON A TIME CLOCK 3) A/C UNIT NOT PER PLAN EQUIPMENT SCHEDULE AND NOTES 4) AIR BALANCE OK |