Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 09/24/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE SECONDARY DRAINS ON UNITS 2) FILER ACCESS BLOCKED BY WIRING 3) OK FOR TILES MECHANICAL ONLY |
|
| 09/20/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE CONICAL TAPS PER PLANS 2) EXPOSE DUCT JOINTS TO VERIFY DUCT SEALER 3) COMPLETE O.S.A. DUCT 4) COMPLETE EXHAUST DUCT 5) PROVIDE 1" THICK REFRIGERANT PIPING INSULATION PER PLANS 6) PROVIDE 36" MINIMUM CLEARANCE TO DISCONNECT |