Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/08/2010 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 10/06/2010 |
ELECTRIC - INTERMEDIATE |
|
Denied |
1) WIRES AGAINST FLOOR TRUSSES IN CEILING OF GARAGE GUSSET |
| 08/26/2010 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :* |