Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2010 | BUILDING - FINAL | Approved | IVRS - Inspection :$ | |
| 12/06/2010 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABEL ALL BREAKERS AT PANEL 2) LABEL UNIT NUMBERS FOR A/C COMPRESSORS AT DISCONNECTS AND PANEL 3) MAX FUSE DISCONNECT FOR SMALL COMPRESSOR OF 30 AMP 4) ENERGY CERT POSTED AT PANEL 5) FINAL INSPECTION ON SPRINKLER SYSTEM 6) POST TENSION LABEL AT HOSE BIB 7) LEVEL A/C COMPRESSORS 8) NO POWER TO EXTERIOR OUTLETS ? 9) NEED LADDER TO INSPECT FAN UNIT IN ATTIC |