Permit: T10CM02143

Parcel: 141353900

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T10CM02143

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
10/08/2010 FRAMING Approved
10/06/2010 FRAMING Denied 1) DRAFT STOP FLOOR TRUSSES PER R502.12
2) REPLACE BROKEN NAILER FOR GYP SUM SHEARWALL AT CEILING IN EAST GARAGE WALL
3) CARRY BEARING TO FOUNDATION FOR TRIMMERS UNDER RAFTER GIRDER AT FRONT OF HOUSE AND GARAGE
4) 602 DETAIL MISSING AT EACH END OF GLUE LAMB BETWEEN DINING AND FAMILY ROOM
5) CARRY BEARING TO FOUNDATION AT BEARING POINTS AT BACK WALL
6) 3-2 X 4 POSTS UNDER HEADER FOR FRONT WINDOW NEXT TO FRONT DOOR