Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/24/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) REFER TO UNIT MANUFACTURERS INSTALLATION INSTRUCTIONS FOR PROPER FILTER APPLICATION, PROVIDE FILTER ACCESSARY KIT IF NEEDED
02/01/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE PROPER FILTER RACK, UNABLE TO REMOVE FILTER WITHOUT BENDING
2.REMOVE ALL FOIL TAPE FROM FLUE PIPING
3.PROVIDE APPROVED CORD CONNERCTOR WHERE WIRING ENTERS CABINET
4.PROVIDE FACTORY GREMMET WHERE LINE SETS ENTER COIL CABINET
5.CONDENSATE PUMP NOT WIRED AT SAFETY SHUT-OFF
6.PROVIDE SUPPORT OF GAS PIPIN
7.SEAL TITE OUT OF DISCONNECT REQUIRES STRAP WITHING 12"OF BOX
8.DUCT TAPE NOT APPROVED FOR ELECTRICAL