Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/29/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE AIR BALANCE REPORT 2) EVERYTHING ELSE IS OK |
|
| 08/23/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* DUCT SMOKE DETECTOR TEST BY FIRE ALARM COMPANY OK INSULATE LIVE SETS ON ROOF. PROVIDE BUSHINGS AT LINE SETS INTO DONDENSOR. LEVEL CONDENSORS. SOME UNITS OVERFUSED. SEAL AROUND LINE SETS AT ROOF FLASHING. PROVIDE HOSE CLAMPS ON DONDENSATE PUMP DRAIN HOSES. CONNECT OVERFLOR SENSORS. PROVIDE A GRILL ON SMALL FAN COILS. |