Permit: T10CM02102

Parcel: 13316024P


Addresses:

6350 E GRANT RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
04/08/2011 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
04/05/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :* SAMPLING TANK WTEST OK
AREA DRAIN & RWL SW STAIRWELL OK
03/14/2011 PLUMBING - ROUGH, SOIL Partial Approval 1. FOUR INCH SANITARY TIE INTO BRANCH FOM DETAIL SHOP BACK UPSTREAM THROUGH (2) SO-2 PAGE P-2.2 WITH TIE-IN FROM GREASE WASTE PIPING ALREADY COVERED WITH VENTS WATER TEST INCLUDING INTERCEPTORS OK PROVIDE SAMPLING BOX PER PLAN WITH TEST.
03/01/2011 PLUMBING - ROUGH, SOIL Partial Approval 1. TR 159 WITH UTILITY SINK 157
02/28/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
02/25/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) GW TO INTERCEPTORS
2) NEED TO SEE CONNECTIONS TO TDS AND INTERCEPTORS
02/24/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) SOIL PIPE WITH TEST THRU CLEANOUT FITTINGS, WEST OF MATCH LINE WITH TIE IN TO SEWER OK
02/10/2011 PLUMBING - ROUGH, SOIL Partial Approval GANG TOILET ROOMS 120 AND 121 AND MAINS, EXCEPT TOILET ROOM 107.
02/02/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection tr and sinks on west side to col 2ao
02/01/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*4" ABS TIE IN AT 4" ABS SEWER OK
01/28/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
01/27/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) SITE SEWER OK, NEED TO SEE TIE IN TO EXISTING AND TIE IN AT BLDG CONNECTIONS
01/26/2011 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL A 3" CLEANOUT ON URINAL BRANCH 707.11
2) PROVIDE UNIFORM SLOPE THROUGHOUT
3) SITE SEWER HAS BACK PITCH IN AT LEAST 3 LOCATIONS, ALSO I WILL NEED TO INSPECT CONNECTION TO EXISTING SEWER
01/25/2011 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*POST YOUR ADDRESS, 3" C/O REQUIRED FOR 3" WASTE PIPING, HORZONTAL VENTING ALLOWED FOR STRUCTURAL CONDITIONS, SUPPORT PIPING WITH CLEAN FILL, WASTE PIPING LIMITED TO 135 DEGREE,