Permit: T10CM02090

Parcel: 110162770

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/09/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/24/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) MISSING DEVICES
2) MISSING LIGHT FIXTURES
3) INSTALL AFI CIRCUIT PROTECTORS PER PLAN
4) OK EM AND EXIT LIGHTS
5) BOND AROUND CONNECTORS AND A/C UNITS MORE THAN 250V
6) NO TECH SCREWS FOR CONNECTION AT GROUND LUGS
7) GROUND LUGS RATED FOR 1 WIRE TERMINATION
8) CHECK WITH BLDG INSPECTOR FOR TCO