Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T10CM02090
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/18/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
11/02/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CANNOT FEED INCANDESCENT LIGHTS WITH 277V SEE NEC 210.6 (C) 2) OK CEILINGS ROOMS 24,21,20,41,19,23 AND 22 |
|
11/01/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) FAN BOXES MUST BE LISTED FOR FANS |
|
10/29/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RECESSED FIXTURES TO BE FLOURESCENT PER FIXTURE SCHEDULE 2) FAN BOXES FOR LISTED AND MARKED FOR USE 3) NEED TO PROVIDE ACCESS PANELS TO JUNCTION BOXES ABOVE HARD LID |