Permit: T10CM02090

Parcel: 110162770

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T10CM02090

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/18/2010 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
11/02/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) CANNOT FEED INCANDESCENT LIGHTS WITH 277V SEE NEC 210.6 (C)
2) OK CEILINGS ROOMS 24,21,20,41,19,23 AND 22
11/01/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) FAN BOXES MUST BE LISTED FOR FANS
10/29/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RECESSED FIXTURES TO BE FLOURESCENT PER FIXTURE SCHEDULE
2) FAN BOXES FOR LISTED AND MARKED FOR USE
3) NEED TO PROVIDE ACCESS PANELS TO JUNCTION BOXES ABOVE HARD LID