Permit: T10CM02078

Parcel: 136331930


Addresses:

9358 E 33RD ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
11/19/2010 BUILDING - FINAL Approved IVRS - Inspection :*
11/17/2010 BUILDING - FINAL Denied IVRS - Inspection :
A/C -HEAT UNIT NEED TO BE ON DEDICATED CIRCUITS
NEW UNITS A/C ONLY S/B HEAT PUMPS TOO
NEED HEATING TO ADDITION PER CODE
MISSING ANTI-SIPHON VALVES ON HOSE BIBBS EXTERIOR
NEED WATER HAMMERS INSTALLED AT WASHER BOX HOT & COLD SUPPLY
KITCHEN COUNTER RECEPTS NOT GFCI PROTECTED, SHOWING REV POLARITY?
LOAD HINGES AT MAIN DOOR GARAGE
11/12/2010 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*