Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 01/06/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) TESTED DUCT SMOKE DETECTORS IN 10 TON UNITS ONLY FOR FAN SHUT DOWN 2) WHERE ARE THE DUCT SMOKE DETECTORS FOR 3 & 5 TON UNITS PER PLANS ? 3) PROVIDE A LETTER FROM THE ENGINEER IF DELETING ANY DUCT SMOKE DETECTORS 4) STILL NEED TO SEE FIRE ALARM CONNECTIONS TO DUCT SMOKE DETECTORS AT SUPERVISORY PANEL |
|
| 01/04/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED TO TEST DUCT SMOKE DETECTORS |
|
| 10/28/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* |