Permit: T10CM02060

Parcel: 12106001B

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T10CM02060

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2015 FIRE SPKLR - FINAL Approved
11/13/2015 FIRE SPKLR - FINAL Denied No on site to open building
03/05/2014 FIRE SPKLR - FINAL Denied 1. Need sprinkler reports and 5 year check valve are pass due last report on file are dated 05.03.2003 for sprinkler system, 06.30.1998 for 5 year check valve.
2. Need to correct suite numbers on building.
3. Need to replace all painted sprinkler heads
4. Need to add sprinkler coverage in bathroom
NOTE: AN APPROVED PLAN AND PERMIT IS NEEDED BEFORE ANY SPRINKLER WORK TO DONE.