Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2010 | FIRE - FINAL | Approved | Approved 9/9/10 | |
| 09/08/2010 | FIRE - FINAL | Denied | Not approved 8/9/10 1.) Provide a sign on door leading into the warehouse area that readsm, "NOT AN EXIT or EMPLOYEES ONLY'. 2.) Need an EXIT sign for the rear door in the warehouse area. 3.) Remove the locking brackets from the rear exit door in the warehouse area. 4.) Need breaker blanks for electrical panel. 5.) The door between the warehouse area and the shop area must be readily openable without the use of a key. 6.) Need a minimum of three 5 to 10 lb. A-B-C class type portable extinghuishers. a.) must be mounted b.) must be labled c.) must be readily accessable and readily visible d.) must be serviced annually e.) minimum of 30 ft. seperatiopn from each other |