Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T10CM02053
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2010 | FIRE - FINAL | Approved | PER INSP CARD | |
| 12/23/2010 | FIRE - FINAL | Approved | Approved 12/23/10 Must maintain ...... 1.) Must maintaian a clear and unobstructed pathway(exit access)to the exit at all times. 2.) Must remove the diner table located in front of the main exit door 3.) Doors leading to patio allowed to be equipped with thumb-turn provided doors are clearly labled "PATIO" |
|
| 11/09/2010 | FIRE - FINAL | Partial Approval | Partial approval 11/9/10 1.) The drywall under the stairs must sealed with fire rated caulking 2.) The secondary exits require panic hardware. 3.) Need a thumb-turn lock for the exterior storage room. |
|
| 11/05/2010 | FIRE - FINAL | Cancelled | Cancelled 11/5/10 | |
| 10/15/2010 | FIRE - FINAL | Partial Approval | Partial approval OK for TCO 10/15/10 1.) Combustible storage is not allowed under the stairway unless it is protected by a sprinkle or the the walls,ceiling and doors are of 1 hour rating. 2.) Need the striker plate for the front door 3.) Complete installation of panic hardware for main exit . 4.) Provide sign over double-doors adjacent to the main exit reading,"DOOR MUST REMAIN UNLOCKED WHEN THE BUILDING IS OCCUPIED" |
|
| 10/08/2010 | FIRE - FINAL | Partial Approval | OK for TCO 10/8/10 (for training) 1.) Must maintain clear and unobstructive exit path in the kitchen area at all times 2.) Must maintain clear and unobstructive pathway to all exit doors. 3.) Must continue fire and safety practices at all times 4.) Must complete gas line pressure testing by Building |